Maintenance
54
840 USE 115 00 Version 1.0
The
Run
indicator will flash. The
Coll
LED also ma
flash, indicatin
that collisions
are occurrin
on the Ethernet network. Such collisions are normal.
If a fault has occurred, the normal LEDs ma
be extin
uished or other indicators
ma
li
ht. This section will discuss errors reported b
the
Active, Ready, Coll,
Link, Kernel, Appl
and
Fault
indicators.
For each t
pe of error, tr
the su
ested remedies in the order
iven. If no remed
su
ested here overcomes the error, consult
our Schneider Automation customer
representative.
Certain error codes are recorded in the MSTR block. For instructions on how to
read and interpret those codes throu
h Modsoft, please refer to
MSTR Function
Error Codes
on pa
e 28.
6.1.2 Active LED
If the
Active
LED fails to li
ht, the module is not communicatin
with the
backplane.
Troubleshooting 1.
Make sure the Ethernet web embedded server module and the controller are
installed properl
. Verif
that the controller is functionin
.
If the controller is not functionin
, replace it. If neither the new controller nor the
Ethernet module will function, replace the backplane.
2.
Make sure that no more than two network option modules -- includin
NOE,
NOM, NOP and CRP 811 modules -- have been installed in the backplane with
a 140 CPU 113 or 213; no more than six network option modules with a 140
CPU 424, 434 or 534.
3.
Check the version of the controller executive. You must have version 1.1 or
reater to support the Ethernet web embedded server module. Earlier versions
do not reco
nize the module.
4.
Replace and return the fault
Ethernet web embedded server module.
6.1.3 Ready LED
If the
Ready
LED fails to li
ht, the module has failed internal dia
nostic tests.
Troubleshooting 1.
Make sure that power has been applied to the backplane.
2.
Replace and return the fault
Ethernet web embedded server module.